CM-6: Low Voltage (12 to 24 VAC or 12 to 32 VDC)/CM-12: Line Voltage (100-240 VAC)
The CM-6/12 detects Carbon Monoxide (CO) in commercial facilities such as parking garages, boiler rooms, etc. It can be used as a stand-alone detector and controller and as an analog transducer for use with Macurco control panels and other systems.
Made in USA. brand MACURCO, model CM-6/CM-12
International delivery to United Arab Emirates, Kuwait, Qatar, Saudi Arabia, Saudi Arabia, Bahrain, Oman and other Middle Eastern countries.
Our warehouses are located in UAE. Delivery to other countries (Europe, North and South America, Asia, Africa) is discussed individually.
price По запросу
Available
Only the best I&C brands
Our company is a UAE supplier of control and measuring instruments from well-known world brands
Discounts for organisations
We sell high-tech equipment at best prices. We provide really advantageous conditions for partners
Fast delivery across the Middle East
Supply to United Arab Emirates, Kuwait, Qatar, Saudi Arabia, Bahrain, Oman and other countries
Professional advice on device selection
Our specialists are ready to advise you on any technical question. We can find an analogue of any device
Key features
Applications
| Shipping Weight | 1 pound (0 45 kg) |
| Size | 4 1/2 x 4 x 2 1/8 in (11 4 X 11 4 X 5 3 cm) |
| Color | White or Dark gray |
| Connections | plugs/terminals |
| Mounting box | (not included) 4×4 electric |
| Fan relay | 5 A, 240 VAC, pilot duty, SPDT, latching or non-latching |
| Fan relay actuation | selectable at diS (disable), 15 ppm, 25 ppm, 35 ppm (default), 50 ppm or 100 ppm CO |
| Fan Delay Settings | 0, 1, 3 (default), 5 and 10 minutes |
| Fan Relay Minimum Runtime settings | 0 (default), 3, 5, 10 or 15 minutes |
| Fan relay latching or not latching | (default) selectable |
| Alarm relay | 0 5A 120 V, 60 VA |
| Alarm relay actuation | selectable N O (default) or N C |
| Alarm relay settings | diS, 50 ppm, 100 ppm, 150 ppm and 200 ppm (default) |
| Current Loop | 4-20 mA for 0-200 ppm CO, selectable to ‘bAS’ (default), ‘EnH’, OFF |
| Calibration Period Settings | dis(default), 3, 6, 12 and 24 (months) |
| Buzzer | 85 dBA at 10cm settable to off (default) or on |
| Digital display | 3-digit LED selectable to off (default) or on |
| Operating Environment | 0°F to 125° F (-18 o C to 52o C),10 to 90% RH non-condensing |
| 6-Series Low Voltage | |
| Power | 3 W (max) from 12 to 24 VAC or 12 to 32 VDC |
| Current @ 24 VDC | 75 mA in alarm (two relays), 50 mA (fan relay only) and 23 mA standby |
| 12-Series Line Voltage | |
| Power | 100-240VAC (50 TO 60 HZ) |
| Current | 1 0 A MAX |
| Model Number | Gas Type | Range (Units) | Low Level Alarm Adjustable (Default) | High Level Alarm Adjustable (Default) | Expected Sensor Life | Recommended Coverage Area |
| CM-6 | CM-12 | Carbon Monoxide (CO) | 0-200 PPM | 0,15,25,35,50 or 100 PPM | 0,50,100,150 or 200 PPM | 10 Years | Up to 7,500 sq. ft.* |
| Photo | Model | Description |
|---|---|---|
| DVP-120, DVP-120M, DVP-120B, DVP-1200 | Control Panels | |
| PS-24, PS-24-H | Step-down Transformers | |
| DMK-1 | Duct Mount Kit | |
|
HS-A, HS-B, HS-R, HS-C | Horn and Strobe (4 color options) |
|
MRS-485, BRS-485 | Adapter Options |
|
Calibration Kits | Based on Gas Type |
|
WHK-1 | Weatherproof Housing Kit |
You can request the necessary certificates, documentation, instructions and user guide for MACURCO CM-6/CM-12 using the special form.
You can buy MACURCO CM-6/CM-12 in UAE at a price starting from По запросу $ in «Texair FZCO» by leaving a request on the website, by phone +441225535040 or by email rop@texairmeasure.ae. MACURCO CM-6/CM-12 price are subject to change depending on exchange rates. We deliver instruments by transport companies in United Arab Emirates, Kuwait, Qatar, Saudi Arabia, Saudi Arabia, Bahrain and other Middle Eastern countries.