+441225535040

Mon-Fri: 8:00 - 18:00 UAE

Email:

GEORGIN Tia 3 HART Programmable converter

Tia3 temperature converters are aimed at converting signals coming from large panel of input signals:
• Coversion of temperature measurement with RTD100, RTD1000, Ni100, Ni1000 or thermocouple.
• Conversion of linear resistance variation (from level sensors or valves).
• Voltage (mV) and ohmic measurement.
DIN rail mounting
Certified to be installed in explosive atmosphere (see codification).

			int(7617)
NULL
		

Made in France. brand GEORGIN, model Tia 3

International delivery to United Arab Emirates, Kuwait, Qatar, Saudi Arabia, Saudi Arabia, Bahrain, Oman and other Middle Eastern countries.
Our warehouses are located in UAE.

price by request

Available

Available

Advantages

Only the best I&C brands

Our company is a UAE supplier of control and measuring instruments from well-known world brands

Advantages

Discounts for organisations

We sell high-tech equipment at best prices. We provide really advantageous conditions for partners

Advantages

Fast delivery across the Middle East

Supply to United Arab Emirates, Kuwait, Qatar, Saudi Arabia, Bahrain, Oman and other countries

Advantages

Professional advice on device selection

Our specialists are ready to advise you on any technical question. We can find an analogue of any device

Technical specifications of GEORGIN Tia 3

Electrical data

  • Input: Programmable (refer to backside)
  • Output: 4/20 mA
  • Power supply: Standard model – 10V … 30 Vdc.  ATEX version – 10V … 28 Vdc
  • Galvanic isolation: 1500V CA
  • Accuracy: ≤ 0.1% F.S. or ≤ basis accuracy (refer to backside) according to the most important value
  • Load resistance: (Vsupply-10) / 0.0215 Ω
  • Shorted or broken line detection: Configurable 3.5 mA to 21.5 mA (NAMUR NE43)
  • Warm-up time: 5 minutes
  • Response time: < 2 s
  • Drift: Voltage supply: ≤ 0.01% of the current in the loop for a variation of 0.1% of Vsupply. Temperature – ≤ 10% of accuracy / degree
  • Error due to CJC: 1.5x basis accuracy for a cold junction at 0°C to be added
  • Line resistance effect:
    RTD100 2wires* / 3wires** 2.5°C/ Ω
    RTD1000 2wires* / 3wires** 0.25°C/ Ω
    Ni100 2 wires* / 3 wires** 2°C/ Ω
    Ni1000 2 wires* / 3 wires** 0.2°C/ Ω
    * : compensation is configurable / ** : unbalance between wires
  • EMC Immunity < 0.1% F.S.

Mechanical data

  • Housing: Polycarbonate l = 13 mm, h = 110 mm, p = 110 mm
  • Protection: IP 20
  • Weight: approx. 200 g
  • Working T°: -40°C to 85°C (non ATEX version)
  • Storage T°: -40°C to 85°C
  • Relative humidity: 5% to 95% without condensing
  • Connection: Removable screw terminals
  • Max. wire size: from 1×0,2 mm² to 1×2,5 mm²

Certifications

  • EMC: EN 61326 & IEC 61000-6-2
  • For ATEX products and IECEx:
    Intrinsic Safety: EN 60079-0 & IEC 60079-0
    EN 60079-11 & IEC 60079-11
    EN60079-26 & IEC 60079-26
    «n» type of protection: EN 60079-15 & IEC 60079-15
  • Certificate N° Ex ia INERIS 13ATEX0015X & INE13.0022X, Ex nA INERIS 13ATEX3006X & INE13.0023X

User Guide and Instruction manual for GEORGIN Tia 3

You can request the necessary certificates, documentation, instructions and user guide for GEORGIN Tia 3 using the special form.

You can buy GEORGIN Tia 3 in UAE at a favourable price in «Texair FZCO» by leaving a request on the website, by phone +441225535040 or by email . GEORGIN Tia 3 price are subject to change depending on exchange rates. We deliver instruments by transport companies in United Arab Emirates, Kuwait, Qatar, Saudi Arabia, Saudi Arabia, Bahrain and other Middle Eastern countries.