GEORGIN TiXo2 Programmable converter

TiXo2 temperature converters are aimed at converting signals coming from large panel of input signals:
• Conversion of temperature measurement with RTD100, RTD1000, Ni100, Ni1000 or thermocouple.
• Conversion of linear resistance variation (from level sensors or valves).
• Voltage (mV) and ohmic measurement.
These converters are mainly head mounting product and are
certified to be located in explosive atmosphere (see codification).

			int(7631)
NULL
		

Made in France. brand GEORGIN, model TiXo2

International delivery to United Arab Emirates, Kuwait, Qatar, Saudi Arabia, Saudi Arabia, Bahrain, Oman and other Middle Eastern countries.
Our warehouses are located in UAE.

price by request

Available

Available

Advantages

Only the best I&C brands

Our company is a UAE supplier of control and measuring instruments from well-known world brands

Advantages

Discounts for organisations

We sell high-tech equipment at best prices. We provide really advantageous conditions for partners

Advantages

Fast delivery across the Middle East

Supply to United Arab Emirates, Kuwait, Qatar, Saudi Arabia, Bahrain, Oman and other countries

Advantages

Professional advice on device selection

Our specialists are ready to advise you on any technical question. We can find an analogue of any device

Technical specifications of GEORGIN TiXo2

Electrical data

  • Input: Programmable (refer to backside)
  • Output: 4/20 mA
  • Power supply:
    Standard model: 10V … 30 Vdc
    ATEX version: 10V … 28 Vdc
  • Galvanic isolation: 1500V CA
  • Accuracy: ≤ 0.1% F.S. or ≤ basis accuracy (refer to backside) according to the most important value
  • Load resistance: (Vsupply-10) / 0.0215 Ω
  • Shorted or broken line detection: Configurable 3.5 mA to 21.5 mA (NAMUR NE43)
  • Warm-up time: 5 minutes
  • Response time: < 2 s
  • Drift:
    Voltage supply: ≤ 0.01% of the current in the loop for a variation of 0.1% of Vsupply
    Temperature: ≤ 10% of accuracy / degree
  • Error due to CJC: 1.5x basis accuracy for a cold junction at 0°C
  • Line resistance effect
    RTD100 2wires* / 3wires** 2.5°C/ Ω
    RTD1000 2wires* / 3wires** 0.25°C/ Ω
    Ni100 2 wires* / 3 wires** 2°C/ Ω
    Ni1000 2 wires* / 3 wires** 0.2°C/ Ω
    * Compensation is configurable / ** : unbalance between wires
  • EMC Immunity < 0.1% F.S

Mechanical data

  • Housing: Plastic (PBT), Ø = 44 mm H = 21.6 mm
  • Protection: IP 00 on terminals
  • Weight: approx. 40 g
  • Working T°: -40°C to 50°C (non ATEX version)
  • Storage T°: -40°C to 50°C
  • Relative humidity: 5%-95% without condensing
  • Connection: Screw terminals – capture screws
  • Max. wire size: 1x 1.5 mm²

Certifications

  • EMC: EN 61326 & IEC 61000-6-2
  • For ATEX products:
    Intrinsic Safety: EN 60079-0 & EN 61241-0
    EN 60079-11 & EN 61241-11
    EN60079-26
    «n» type of protection: EN 60079-15
  • Certificate N°: INERIS 08ATEX0004X & 08ATEX3002U
  • ATEX Classification:
    CE 0081 II 1 GD Ex ia IIC
    CE 0081 II 1 GD Ex iaD 20
    CE II 3 G Ex nA II
  • Ambiante working T°
    T4 : -40°C < ambiante T° < 85°C
    T5 : -40°C < ambiante T° < 65°C
    T6 : -40°C < ambiante T° < 50°C

User Guide and Instruction manual for GEORGIN TiXo2

You can request the necessary certificates, documentation, instructions and user guide for GEORGIN TiXo2 using the special form.

You can buy GEORGIN TiXo2 in UAE at a favourable price in «Texair FZCO» by leaving a request on the website, by phone +441225535040 or by email . GEORGIN TiXo2 price are subject to change depending on exchange rates. We deliver instruments by transport companies in United Arab Emirates, Kuwait, Qatar, Saudi Arabia, Saudi Arabia, Bahrain and other Middle Eastern countries.